Key Takeaways
- The Autronica 116-BN-310 provides one potential-free changeover (relay) contact, addressable and activatable from any detector on the system.
- SelfVerify automatically checks the unit’s alarm-initiation capability once every 24 hours, with no manual intervention.
- Each unit includes a short-circuit isolator and automatic addressing on the detection loop.
- Rated 10–27 VDC, 0.3 mA standby, contact rated 1 A / 30 VDC resistive, in an IP66-rated (with PG glands) fiberglass-reinforced polycarbonate enclosure.
- Compliant with EN 54-5/EN 54-7 environmental requirements and designed to meet the requirements of the major maritime classification societies.
What Is the Autronica 116-BN-310 Single Relay Output Unit?
The 116-BN-310 is an interface (I/O) unit within Autronica’s I/O product line, built for the AutroSafe and Autroprime interactive fire detection platforms. Instead of detecting fire itself, it converts a digital alarm command from the fire alarm control panel into a physical relay action — a single potential-free changeover contact that can switch an external circuit such as a magnetic door holder, a sprinkler valve solenoid, or a fire damper actuator.
Because the 116-BN-310 is an addressable loop device, it occupies one address on the detection loop and can be configured so its contact is activated by any detector, or logical combination of detectors, anywhere in the system — it is not restricted to devices wired on the same physical loop segment. This gives system designers flexibility to build cause-and-effect (C&E) logic across zones without adding extra field wiring.
How Does the SelfVerify Function Work on the Autronica 116-BN-310?
SelfVerify is Autronica’s automatic self-testing technology: every SelfVerify-equipped unit, including the Autronica 116-BN-310, verifies its own ability to activate once every 24 hours without manual intervention. This is the same reliability principle used across Autronica’s interactive detector and call point range, applied here to an output device.
For engineering teams and facility operators, this delivers three practical benefits:
- Lower maintenance overhead: routine functional checks of each relay output are performed automatically by the system, reducing the number of units technicians must test by hand during scheduled maintenance rounds.
- Documented compliance: the control panel logs each self-test cycle, giving an auditable record that every relay output on the loop is functional — useful evidence during classification surveys and fire authority inspections.
- Faster fault detection: a unit that fails its self-test is reported immediately to the panel, instead of remaining silently non-functional until the next scheduled manual test.
Key Features of the Autronica 116-BN-310
- Interactive, addressable loop device with automatic addressing — no manual configuration
- One potential-free changeover (SPDT) contact, rated 1 A at 30 VDC resistive
- SelfVerify function — automatic self-test every 24 hours
- Built-in short-circuit isolator in every unit
- Activatable from any detector in the system, regardless of physical loop
- Proven technology, designed to meet the requirements of the major maritime classification societies
- Compliant with EN 54-5/EN 54-7 environmental requirements
The short-circuit isolator built into every 116-BN-310 matters at the system level: on a loop architecture, a single cable fault could otherwise disable every device downstream. Because isolation happens at the device, a fault is contained between two adjacent units, and the rest of the loop — including other relay outputs controlling dampers or sprinklers elsewhere in the facility — keeps operating. That containment is a key design consideration for high-consequence sites such as offshore platforms, LNG terminals and data centers.
Autronica 116-BN-310 Technical Specifications
| Parameter | Value |
|---|---|
| Part number | 116-BN-310 |
| Output | 1 potential-free changeover contact, max. 1 A – 30 VDC resistive |
| Voltage | 10 – 27 VDC |
| Current consumption (standby) | 0.3 mA |
| Weight | 175 g |
| Material | Fiberglass-reinforced polycarbonate (PC + GF10%) |
| Colour | Light grey |
| Degree of protection | IP54 (membrane inlets) / IP66 (PG-13.5 inlets) |
| Working temperature | −20 °C to +70 °C |
| Humidity (non-condensing) | Max. 95% RH |
| Environmental requirement | EN 54-5 / EN 54-7 |
| Maintenance | None |
| Service policy | Replace if faulty |
Source: Autronica Fire and Security AS, Autronica 116-BN-310 Product Datasheet (Doc-1000376-2, 2026).
Wiring and Connections of the Autronica 116-BN-310
The 116-BN-310 connects in-line on the detection loop through four active loop terminals: Pos (+) in, Pos (+) out, Neg (−) in and Neg (−) out. The relay contact itself is wired separately through three terminals: Normally Open, Normally Closed and Common, giving installers the choice of a fail-open or fail-closed configuration depending on the controlled circuit (door holder, damper actuator or sprinkler valve solenoid). Four additional terminals on the unit are marked “N.A.” (not for use).
Because the short-circuit isolator sits inside the unit itself, loop segmentation happens automatically around any cable fault — a relevant factor when calculating loop load and planning cause-and-effect wiring across several 116-BN-310 units on the same circuit. External controlled devices cannot be powered directly from the detector loop and require their own power supply.
Where the Autronica 116-BN-310 Is Applied
As an output unit within the AutroSafe and Autroprime interactive platforms, the 116-BN-310 is specified wherever a fire alarm event needs to trigger a physical action rather than only an audible/visual alarm:
- Door release: holding fire doors open under normal conditions and releasing them on alarm to restore compartmentation.
- Sprinkler control/functions: interfacing detection logic with sprinkler valve actuation circuits.
- Fire damper control: closing HVAC dampers to prevent smoke spread through ductwork.
- Oil & gas, offshore and petrochemical facilities: integrated into AutroSafe/Autroprime cause-and-effect matrices across process areas, accommodation modules and technical buildings — a growing requirement across the European oil & gas market.
- Maritime and offshore installations: designed to meet the requirements of the major classification societies, supported by an IP66-rated enclosure for harsher shipboard environments.
- Data centers: relay-controlled damper and door interfaces as part of a broader fire protection strategy — see our guide to fire protection for data centers.
Related I/O Units in the Autronica Range
The 116-BN-310 sits within a broader family of interface units used to build cause-and-effect logic on the detection loop:
| Part Number | Description |
|---|---|
| 116-BN-310 | Single relay output unit (this article) |
| 116-BN-320 | Interface unit with SelfVerify |
| 116-BNA-320/06 | Interface board |
| 116-BNB-300/02 | Interface module |
| 116-6571-011.6020 | M20 membrane gland (4 glands included with the 116-BN-310) |
Selecting between these depends on the number of outputs required per address and the specific interface logic needed — our engineering team can help map the correct combination to your cause-and-effect matrix.
Frequently Asked Questions About the Autronica 116-BN-310
What does the Autronica 116-BN-310 do?
The Autronica 116-BN-310 is a single relay output unit for Autronica’s interactive fire detection systems. It provides one potential-free changeover contact that activates from a detector, or combination of detectors, anywhere in the system, and is used for door release, sprinkler control/functions and fire damper control.
How many outputs does the 116-BN-310 have?
The unit has one output — a single potential-free changeover contact rated at a maximum of 1 A at 30 VDC resistive, occupying one address on the detection loop.
What does SelfVerify do on the BN-310?
SelfVerify automatically checks the unit’s ability to activate its relay output once every 24 hours, without manual intervention, reducing the need for routine manual functional testing while maintaining a high level of reliability.
Can the Autronica 116-BN-310 be activated by a detector on a different loop?
Yes. The output can be activated from any detector in the system, not limited to detectors connected to the same physical loop, allowing cause-and-effect logic to be configured across the entire installation.
Which fire detection systems is the 116-BN-310 compatible with?
The Autronica 116-BN-310 is designed for Autronica’s interactive fire detection systems, including the AutroSafe and Autroprime platforms.
Can the BN-310 power the external device it controls?
No. External units, such as door holders or damper actuators, cannot be powered by the detector loop and require an independent power supply; the unit only provides the relay switching contact.
Specify the Autronica 116-BN-310 for Your Project
Blue BMS is a global distributor of Autronica fire detection systems for oil & gas, maritime, data center and industrial applications. Our engineering team supports loop design, cause-and-effect mapping, product selection and international logistics.